top of page
OIL HYDRAULIC ACTUATED
VALVE

The Hydrocore oil-hydraulic actuated valve is used for remote isolating of pipeline applications and mainly used in: Industrial Water Systems, Municipal Water Supply Systems, Pump Stations, Mine Water Reticulation and Petrochemical Plants 

Once an electrical signal is given, the solenoid valve switches over, hydraulic fluid enters the cylinder opening compartment and pulls the valves shuttle towards the open position. Once power is removed the solenoid valve switches to the original position, hydraulic fluid enters the cylinder closing compartment and pushes the valve shuttle to the closed position. In the event of a power failure, the power pack’s accumulator, provides enough oil pressure and oil volume to close the valve. The open and closing speeds can be set separately to prevent water hammer when the valve closes.

HCA OIL HYDRAULIC ACTUATED VALVE.png
HCA OIL-HYDRAULIC ACTUATED VALVE - CS.png
FEATURES
  • Does not need a gearbox to operate

  • Superior flow coefficient (Cv/Kv)

  • Throttles and maintains the pump pressure when the downstream column is empty or partially full

  • Throttles the pump outlet when the pump is stopped to prevent water hammer

  • Can be maintained in line

  • High cavitation resistance due to design

  • Stainless steel moving internals parts

  • Cast steel body 

  • Low pressure drop across valve

  • Flanges and face-to-face dimensions to customer specification

  • Manual override on actuator

  • Electric specifications to suit customer specifications

  • No possibility of contaminating of the actuating fluid.

SPECIFICATIONS
FLOW COEFFICIENTS & FLOW RATES

Actuator

To suit customer specification

Pressure rating

160 bar (max) working pressure

Temperature rating

Up to 85ºC with standard seals.

Media

Liquid and gas with low content of suspended solids.

Pipe sizes

2” (50 NB) to 16” (400 NB)

Flanges

SABS 1123, BS4504, BS10, ASME B16.34, ANSI B16.5

pH levels & chlorides

Parts of the valve are made from stainless steel and can withstand a low level of chlorides.

Installation position

The valve can be installed in any position

 

Seating

Seat Leakage - B16.104 class III, IV, V or VI, depends on valve type and application.

150 NB

Cv/Kv: 525 | Flow (max): 117 ℓ/sec | ΔP: 12.5 psi

200 NB

Cv/Kv: 1086 | Flow (max): 152 ℓ/sec | ΔP: 1.4 psi

250 NB

Cv/Kv: 1433 | Flow (max): 233 ℓ/sec | ΔP: 6.7 psi

300 NB

Cv/Kv: 1936 | Flow (max): 337 ℓ/sec | ΔP: 7.9 psi

DIMENSIONS AND WEIGHTS
HCA OIL-HYDRAULIC ACTUATED VALVE - SPECS.png

SIZE

 

150 NB

200 NB

250 NB

300 NB

A (mm)

381

494

573

652

B (mm)

TBD

TBD

929

TBD

C (mm)

TBD

TBD

1743

TBD

#150 F-T-F

 

559mm / 229kg

660mm / 405kg

787mm / 744kg

838mm / 1052kg

#300 F-T-F

 

59mm / 245kg

660mm / 429kg

787mm / 778kg

838mm / 1098kg

#600 F-T-F

 

559mm / 270kg

660mm / 460kg

787mm / 840kg

838mm / 1164kg

#900 F-T-F

610mm / 297kg

737mm / 509kg

838mm / 891kg

965mm / 1277kg

#1500 F-T-F

705mm / TBD

832mm / TBD

991mm / TBD

1130mm / TBD

bottom of page