PRESSURE REDUCING
STATION
The Hydrocore™ Pressure Reducing Station includes a fully assembled station, complete with isolating valves, strainers, pressure reducing valves and a relief valve, as well as all the accessory components such as gauges, ball valves, etc.
​
Our stations can be setup horizontally or vertically, and in dual leg formation.
HORIZONTAL DUAL LEG STATION
VERTICAL DUAL LEG STATION
SPECIFICATIONS
FLOW COEFFICIENTS & FLOW RATES
​Pressure rating
Sizes 50NB ~ 100NB: 250 bar (max)
Sizes 150NB ~ 300NB: 160 bar (max)
​
Temperature rating
Up to 85ºC with standard seals.
​
Media
Liquid and gas with low content of suspended solids.
​
Pipe sizes
2” (50 NB) to 16” (400 NB)
​
Flanges
SABS 1123, BS4504, BS10, ASME B16.34, ANSI B16.5
​
pH levels & chlorides
Parts of the valve are made from stainless steel and can withstand a low level of chlorides.
​
Installation position
The valve can be installed in any position
Seating
Seat Leakage - B16.104 class III, IV, V or VI, depends on valve type and application.
50 NB
Cv/Kv: 50 | Flow (max): 9 â„“/sec
​
80 NB
Cv/Kv: 97 | Flow (max): 25 â„“/sec
​
100 NB
Cv/Kv: 132 | Flow (max): 38 â„“/sec
​
150 NB
Cv/Kv: 325 | Flow (max): 117 â„“/sec
​
200 NB
Cv/Kv: 648 | Flow (max): 152 â„“/sec
​
250 NB
Cv/Kv: 871 | Flow (max): 233 â„“/sec
​
300 NB
Cv/Kv: 1500 | Flow (max): 337 â„“/sec